DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
DeWalt petrol generators are fitted with a low-oil sensor that will stop the generator from starting if there is not enough oil in the motor. This can also activate if the generator is not on a level surface.
INV-P1-Q1: Have you checked the dipstick and confirmed that the oil is full? Check the oil and fill if required.
INV-P1-Q2: Is the petrol tank full? Check the oil and fill if required.
INV-P1-Q3: Is the engine switch set to the CHOKE position? Turn the engine switch to the CHOKE position.
INV-P1-Q4: Have you removed the spark plug and checked it is dry and clean (see manual for more information)? Clean the spark plug as outlined in the manual and try again.
It is possible that there is fuel inside the engine. Dry the spark plug and try again. If the spark plug is still wet it will need to be sent to an Authorised Repair Agent by completing this form.
The spark plug should be checked to ensure it is able to provide a spark. Please check and retry.
Check the manual for instructions on how to remove the spark plug. If you are still unsure, please send to an Authorised Repair Agent by completing this form.
DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
DeWalt petrol generators are fitted with a low-oil sensor that will stop the generator from starting if there is not enough oil in the motor. This can also activate if the generator is not on a level surface.
INV-P2-Q1: Have you checked the dipstick and confirmed that the oil is full? Check the oil and fill if required.
INV-P2-Q2: Is the generator on a level surface? The generator needs to be on a level surface or the low-oil system may shut it down. Place on a level surface and try again.
INV-P2-Q3: Once the motor starts, the choke should be set at the RUN position. Have you set the choke to the RUN position after starting? Once the motor starts, set the choke to the RUN position.
INV-P2-Q4: Is the fuel tank full of fuel? Fill the fuel tank and try again.
INV-P2-Q5: Have you removed the spark plug and checked it is dry and clean (see manual for more information)? Clean the spark plug as outlined in the manual and try again.
It is possible that there is fuel inside the engine. Dry the spark plug and try again. If the spark plug is still wet it will need to be sent to an Authorised Repair Agent by completing this form.
The spark plug should be checked to ensure it is able to provide a spark. Please check and retry.
Check the manual for instructions on how to remove the spark plug. If you are still unsure, please send to an Authorised Repair Agent by completing this form.
DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
DeWalt petrol generators are fitted with a circuit breaker that stops power going to the outlets.
INV-P3-Q1: Have you tried resetting the circuit breaker? Reset the circuit breaker and try again.
INV-P3-Q2: Have you confirmed that the appliance works in another power outlet? Check the appliance works in another power outlet to make sure the appliance is in good working order.
DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
This generator’s max peak watts is 2200 and max rated watts is 1800.
The load that you connect should not exceed this rating.
INV-P4-Q1: Does the appliance(s) that you connect exceed this rating? If the appliance(s) connected exceed the rating of the generator, it will cause the generator to overload and the circuit breakers will trip. Remove the appliance(s) and try again.
INV-P4-Q2: Does the circuit breaker trip when no appliance is connected? INV-P4-Q3: The fault may be in the appliance. Have you tested the appliance works in another outlet? There may be an issue with the appliance. Check that it works in a different power source.
DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
The DXIG3600E and DXIG3601E have an automatic choke and MUST be connected to a working battery.
Please ensure that the battery is in good working order and is connected. See instruction manual for more information.
INVBAT-P1-Q1: Is the battery charged and connected to the generator? Charge the battery and try again.
Connect the battery and try again.
INVBAT-P1-Q2: Have you checked the dipstick and confirmed that the oil is full and ensured there is enough fuel in the tank? Ensure that the oil and fuel is full before continuing.
INVBAT-P1-Q3: Is the fuel valve in the ON position? Turn the fuel valve on and try again.
INVBAT-P1-Q4: Is the engine switch in the ON position? Set the engine switch to the ON position and try again.
INVBAT-P1-Q5: Have you removed the spark plug and checked it is dry and clean (see manual for more information)? Clean the spark plug as outlined in the manual and try again.
It is possible that there is fuel inside the engine. Dry the spark plug and try again. If the spark plug is still wet it will need to be sent to an Authorised Repair Agent by completing this form.
The spark plug should be checked to ensure it is able to provide a spark. Please check and retry.
Check the manual for instructions on how to remove the spark plug. If you are still unsure, please send to an Authorised Repair Agent by completing this form.
DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
DeWalt petrol generators are fitted with a low-oil sensor that will stop the generator from starting if there is not enough oil in the motor. This can also activate if the generator is not on a level surface.
INVBAT-P2-Q1: Have you checked the dipstick and confirmed that the oil is full? Check the oil and fill if required.
INVBAT-P2-Q2: Is the generator on a level surface? The generator needs to be on a level surface or the low-oil system may shut it down. Place on a level surface and try again.
INVBAT-P2-Q3: Is the fuel valve in the ON position? Turn the fuel valve on and try again.
INVBAT-P2-Q4: Is the engine switch in the ON position? Set the engine switch to the ON position and try again.
INVBAT-P2-Q5: Have you removed the spark plug and checked it is dry and clean (see manual for more information)? Clean the spark plug as outlined in the manual and try again.
It is possible that there is fuel inside the engine. Dry the spark plug and try again. If the spark plug is still wet it will need to be sent to an Authorised Repair Agent by completing this form.
The spark plug should be checked to ensure it is able to provide a spark. Please check and retry.
Check the manual for instructions on how to remove the spark plug. If you are still unsure, please send to an Authorised Repair Agent by completing this form.
DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
DeWalt petrol generators are fitted with a circuit breaker that stops power going to the outlets.
INVBAT-P3-Q1: Have you tried resetting the circuit breaker? Reset the circuit breaker and try again.
INVBAT-P3-Q2: Have you confirmed that the appliance works in another power outlet? Check the appliance works in another power outlet to make sure the appliance is in good working order.
Check the appliance works in another power outlet to make sure the appliance is in good working order.
DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
This generator’s max peak watts is 3600 and max rated watts is 3200.
The load that you connect should not exceed this rating.
INVBAT-P4-Q1: Does the appliance(s) that you connect exceed this rating? If the appliance(s) connected exceed the rating of the generator, it will cause the generator to overload and the circuit breakers will trip. Remove the appliance(s) and try again.
INVBAT-P4-Q2: Does the circuit breaker trip when no appliance is connected? INVBAT-P4-Q3: The fault may be in the appliance. Have you tested the appliance works in another outlet? There may be an issue with the appliance. Check that it works in a different power source.
DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
The battery needs to be connected and charged for the key start to work.
INVBAT-P5-Q1: Is the battery charged and connected to the generator? Charge the battery and try again.
Connect the battery and try again.
INVBAT-P5-Q2: Will the generator start using the recoil starter? INVBAT-P5-Q3: Have you checked that there is fuel and oil? Check and fill the fuel and oil and try again.
INVBAT-P5-Q4: Have you removed the spark plug and checked it is dry and clean (see manual for more information)?* Clean the spark plug as outlined in the manual and try again.
It is possible that there is fuel inside the engine. Dry the spark plug and try again. If the spark plug is still wet it will need to be sent to an Authorised Repair Agent by completing this form.
The spark plug should be checked to ensure it is able to provide a spark. Please check and retry.
Check the manual for instructions on how to remove the spark plug. If you are still unsure, please send to an Authorised Repair Agent by completing this form.
DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
DeWalt petrol generators are fitted with a low-oil sensor that will stop the generator from starting if there is not enough oil in the motor. This can also activate if the generator is not on a level surface.
INV7000-P1-Q1: Have you checked the dipstick and confirmed that the oil is full? Check the oil and fill if required.
INV7000-P1-Q2: Is the petrol tank full? Fill with fuel and try again.
INV7000-P1-Q3: Is the fuel valve in the ON position? Turn the fuel valve on and try again.
INV7000-P1-Q4: Is the choke set to CHOKE? Set the choke to the CHOKE position and try again.
INV7000-P1-Q5: Is the engine switch in the ON position? Turn the engine switch to the ON position and try again.
INV7000-P1-Q6: Have you removed the spark plug and checked it is dry and clean (see manual for more information)? Clean the spark plug as outlined in the manual and try again.
It is possible that there is fuel inside the engine. Dry the spark plug and try again. If the spark plug is still wet it will need to be sent to an Authorised Repair Agent by completing this form.
The spark plug should be checked to ensure it is able to provide a spark. Please check and retry.
Check the manual for instructions on how to remove the spark plug. If you are still unsure, please send to an Authorised Repair Agent by completing this form.
DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
DeWalt petrol generators are fitted with a circuit breaker that stops power going to the outlets.
INVPK-P1-Q1: Have you tried resetting the circuit breaker? Reset the circuit breaker and try again.
INVPK-P1-Q2: Have you confirmed that the appliance works in another power outlet? Check the appliance works in another power outlet to make sure the appliance is in good working order.
DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
This generator’s max peak watts is 4400 and max rated watts is 3600.
The load that you connect should not exceed this rating.
INVPK-P2-Q1: Does the appliance(s) that you connect exceed this rating? If the appliance(s) connected exceed the rating of the generator, it will cause the generator to overload and the circuit breakers will trip. Remove the appliance(s) and try again.
INVPK-P2-Q2: Does the circuit breaker trip when no appliance is connected? INVPK-P2-Q3: The fault may be in the appliance. Have you tested the appliance works in another outlet? There may be an issue with the appliance. Check that it works in a different power source.
DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
DeWalt petrol generators are fitted with a low-oil sensor that will stop the generator from starting if there is not enough oil in the motor. This can also activate if the generator is not on a level surface.
INV36-P1-Q1: Have you checked the dipstick and confirmed that the oil is full? Check the oil and fill if required.
INV36-P1-Q2: Is the petrol tank full? Fill with fuel and try again.
INV36-P1-Q3: Is the fuel valve in the ON position? Turn the fuel valve on and try again.
INV36-P1-Q4: Is the choke set to CHOKE? Set the choke to the CHOKE position and try again.
INV36-P1-Q5: Is the engine switch in the ON position? Turn the engine switch to the ON position and try again.
INV36-P1-Q6: Have you removed the spark plug and checked it is dry and clean (see manual for more information)? Clean the spark plug as outlined in the manual and try again.
It is possible that there is fuel inside the engine. Dry the spark plug and try again. If the spark plug is still wet it will need to be sent to an Authorised Repair Agent by completing this form.
The spark plug should be checked to ensure it is able to provide a spark. Please check and retry.
Check the manual for instructions on how to remove the spark plug. If you are still unsure, please send to an Authorised Repair Agent by completing this form.
DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
DeWalt petrol generators are fitted with a low-oil sensor that will stop the generator from starting if there is not enough oil in the motor. This can also activate if the generator is not on a level surface.
INV36-P2-Q1: Have you checked the dipstick and confirmed that the oil is full?* Check the oil and fill if required.
INV36-P2-Q2: Is the generator on a level surface?* The generator needs to be on a level surface or the low-oil system may shut it down. Place on a level surface and try again.
INV36-P2-Q3: Is the fuel valve in the ON position?* Turn the fuel valve on and try again.
INV36-P2-Q4: Once the motor starts, the choke should be set at the RUN position. Have you set the choke to the RUN position after starting?* Set the choke to the RUN position after the generator starts.
INV36-P2-Q5: Is the fuel tank full of fuel?* Fill with fuel and try again.
INV36-P2-Q6: Have you removed the spark plug and checked it is dry and clean (see manual for more information)?* Fill with fuel and try again.
It is possible that there is fuel inside the engine. Dry the spark plug and try again. If the spark plug is still wet it will need to be sent to an Authorised Repair Agent by completing this form.
The spark plug should be checked to ensure it is able to provide a spark. Please check and retry.
Check the manual for instructions on how to remove the spark plug. If you are still unsure, please send to an Authorised Repair Agent by completing this form.
DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
DeWalt petrol generators are fitted with a circuit breaker that stops power going to the outlets.
INV36-P3-Q1: Have you tried resetting the circuit breaker?* Reset the circuit breaker and try again.
INV36-P3-Q2: Have you confirmed that the appliance works in another power outlet?* Check the appliance works in another power outlet to make sure the appliance is in good working order.
DISCONNECT ALL APPLIANCES BEFORE CONTINUING.
This generator’s max peak watts is 3600 and max rated watts is 3200.
The load that you connect should not exceed this rating.
INV36-P4-Q1: Does the appliance(s) that you connect exceed this rating?* If the appliance(s) connected exceed the rating of the generator, it will cause the generator to overload and the circuit breakers will trip. Remove the appliance(s) and try again.
INV36-P4-Q2: Does the circuit breaker trip when no appliance is connected?* INV36-P4-Q3: The fault may be in the appliance. Have you tested the appliance works in another outlet?* There may be an issue with the appliance. Check that it works in a different power source.
Section Break Looks like the generator needs to be sent to a DeWalt Authorised Service Agent. Please complete the below and one of the Mayo team will be in contact with you shortly.